Product Catalog
Fire resistant cables

Fire-resistant halogen-free power cables FE180/E90 PvPGng-FRHF (NHXH FE180/E90)

Кабель силовой огнестойкий безгалогеновый ПвПГнг-FRHF (FE180/E90)

Application

Fire resistant power cables, halogen free compounds insulated and sheathed are intended for power supply to fire protection equipment which is to operate in fire conditions (e.g. water pumps in fire extinguishing systems, smoke removing fans). Halogen free cables shall be applied in locations where, in case of fire, higher safety for human beings and expensive electronic equipment is required.
Functions of the cables are maintained – power is supplied to equipment which must operate in fire conditions and during firefighting. The cables are flame retardant and their smoke emission is low, emitted fumes are non-toxic and non-corrosive. The cables are suitable for indoor and outdoor installations.

Construction

1. Conductor: bare copper, solid or stranded (acc. to EN 60228 class 1 or 2);
2. Insulation: mica tape and halogen free cross-linked compound;
3. Inner sheath: halogen free compound;
4. Outer sheath: halogen-free compound (Orange color. Other color upon customer's request).

Requirements compliance

TS U 31.3-00217099-021:2005;
DSTU EN 60228;
DSTU IEC 60502.

Technical-Operational characteristics

Operating temperature range  
during operation from -50°С to +50°С
during installation from -15°С to +50°С
Maximum conductor operating temperature: +90°С
Minimum bending radius:  
- single core cable 10 cable diameter
- multi core cable 7,5 cable diameter
Operating voltage 0.6/1 kV
Insulation integrity FE 180 DSTU 4809:2007, (750°C, 180 min.), IEC 60331-21
System integrity E 90 DSTU 4809:2007, (90 min.)
Flame propagation DSTU 4809:2007, IEC 60332-3-22
Smoke density DSTU 4809:2007, IEC 60332-3-22
Gases evolved during combustion DSTU 4809:2007, IEC 60754-2
No records found.

MOD_BARCODE_MOD_TITLE

MOD_BARCODE_BUHTA

MOD_BARCODE_BARABAN