Power cables with XLPE insulation 6-35 kV

Single or three core XLPE insulated cables with polyethylene outer sheath, longitudinally watertight APvEgP / PvEgP 6-35kV

Кабели силовые с изоляцией из сшитого полиэтилена АПвПг, ПвПг на напряжение 6-35 кВ

Application

Power cables with XLPE insulation for rated voltages U0/U(Um) from 3,6/6 (7,2) kV up to and including 20,8/35 (42) kV at 50 Hz AC.
Uo - phase to ground voltage.
U - rated phase to phase voltage.
Um - maximum voltage (permissible highest voltage for which the equipment is specified).
Cables are suitable for installation in the following areas:
- in soil (trenches), despite the corrosiveness degree of soils, if protected from mechanical damage;
- in the air, including cable structures, if provided the additional fire protection;
- on difficult route sections, with unlimited difference of elevation.

Construction

1. Conductor: aluminium or copper stranded compacted round core, acc. to EN 60228 class 2;
2. Inner extruded semiconductive layer (conductor screen): cross-linked PE-compound;
3. Insulation: XLPE;
4. Outer extruded semiconductive layer (insulation screen): cross-linked PE-compound;
5. Lapping layer: semiconductive swellable water-blocking tape;
6. Screen: copper wires fastened with a copper tape;
7. Separating layer: swellable water-blocking tape(for three core cable-extruded filling of PVC );
8. Outer sheath: polyethylene.

Design options:

APvEgPng-HF, PvEgPng-HF - cables with halogen-free & flame retardant performance.

Requirements compliance

International: IEC 60502-2; CENELEC HD 620 S2 / 605 S2; IEC 60840;
National: TS U 27.3-05758730-093:2017;
Flammability: IEC 60332-1-2, DSTU IEC 60332-1-2, DSTU 4809.

Technical-operational characteristics

Ambient temperature, °С from -60°С to +50°С
Continious permissible conductor temperature +90°С
Maximum permissible conductor temperature at short circuit +250°С
Maximum permissible temperature of copper screen at short circuit +350°С
Maximum permissible conductor temperature during a short circuit under condition of non-ignition of the cable (duration of the short circuit should not exceed 5 sec.) +400°С
Maximum permissible conductor temperature in emergency operation 130 °С
Duration of the cable in emergency operation should not be more than 8 hours per day and not more than 1000 hours for the service life 8 hours per day;
1000 hours for service life
Installation of the cables without prior heating should be carried out at temp., not less than -15°С
Minimum bending radius by laying:  
- single core cable not less than 20 overall diam
- three core cable not less than 15 overall diam
Warranty period: 5 years from the date of commissioning of the cables, but not more than 6 years from the date of manufacture;
The minimum cable life is 40 years. The actual service life is not limited to the specified period, but is determined by the technical condition of the cable
No records found.
Attachments

APPENDIX A1. Reference information on the outer diameter and the estimated weight of power cables for voltage 6-35 kV - Download

APPENDIX A2. Reference information on permissible current loads of power cables for voltage 6-35 kV - Download

APPENDIX A3. Correspondence table of brands of power cables for voltage 6-35 kV (Ukraine - EU) - Download