Cables for the industrial interface armored KIF-PKG (KIPvEPKG)
KIF-PKG (KIPvEPKG) Nx2x0.78
Application
Cables are designed for high-speed data transfer in accordance with ISO / IEC 8482, EIA RS-485 (TIA / EIA-485-A). For outdoor installation in telephone conduits, in sewers, mines, along the walls of buildings in case of danger of damage by rodents.
Cable design
1. Conductor: copper wire 0.78 mm
2. Insulation: FHDPE.
3. Shield Material: aluminum foil + tinned copper braid
4. Copper tinned contact wire
5. Sheath: UV-stabilized PE
6. Braid: galvanized steel wire
Installation and operation conditions
Temp Rating:
- Installation Temp Rating -10 °C ... +60 °C;
- Operating Temp Range: -50 °C ... +60 °C.
Min Bend Radius: ≥ 15
Minor Axis: ≤ 450 N.
Standards
ISO IEC 8482, EIA RS-485 (ТIA/EIA-485-A)
Main technical and mechanical characteristics
Electrical parameter at 20 ° C | Frequency, kHz | Value |
Test voltage for 1 min, kV - between all cores and the screen: - between the veins of the pair: |
D.C. 0,05 D.C. 0,05 |
0,7 0,5 1,4 1,0 |
Conductor electrical resistance, Ohm / km, no more than | D.C. | 59 |
Electrical insulation resistance,per 1 km, t. 20 C, MΩ, not less | D.C. | 150 |
Conductor pair electric capacitance, pF / m | from 0,8 to 1,0 | 40±4 |
Average wave impedance, Ohm | 1000 | 120 ± 12 |
Аttenuation, no more, dB / 100m | 1000 | 1,65 |
Nomenclature and mass-dimensional characteristics
Cable brand | Outside diameter, mm | Weight, kg/km |
KIF-PKG 1х2х0,78 | 8,1 | 85,9 |
KIF-PKG 1,5х2х0,78 | 8,7 | 97,3 |
KIF-PKG 2х2х0,78 | 11,8 | 127,9 |
KIF-PKG 3х2х0,78 | 13,8 | 139,5 |
KIF-PKG 4х2х0,78 | 14,2 | 161,0 |