Product Catalog
Cables for industrial network ProfiBus-DP

BUS 1 * 2 * 0.64V K-2

BUS 1*2*0,64 В К-29

Application

Symmetrical twisted pair cables are designed for single stationary installation in industrial automation systems for technological processes and transmission networks in hazardous areas built in acc.  PROFIBUS IEC 61158-2 and ISA / SP 50 (Foundation Fieldbus) specifications. Cables are used indoors and outdoors, provided that they are protected from direct exposure of sunlight and precipitation.

Cable design

1. Conductor: copper wire 0.64 mm
2. Insulation: FHDPE
3. Shield material: aluminum foil + tinned copper braid
4. Copper tinned contact wire
5. Sheath: PE

Installation and operation conditions

Temp Rating:
- Installation Temp Rating: -10 °C ... +50 °C;
- Operating Temp Range: -20 °C ... +60 °C.

Standards

PROFIBUS IEC 61158-2

Main technical and mechanical characteristics

Electrical parameter at 20 ° C Frequency, kHz Value
Еest voltage for 1 min, kV
- between cores and the screen:

D.C.
0,05

0,7
0,5
1,4
1,0
Pair electric capacitance, pF / m from 0,8 to 1,0 35,0
Impedance, ohm 1000 150 ± 15
Attenuation, no more than, dB / 100m 1000 12
Conductive core electrical resistance, Ohm / km, no more than D.C. 63,0
Electrical insulation resistance, per 1 km of length and t. 20 С, MΩ, not less than D.C. 150

Nomenclature and mass-dimensional characteristics

Cable brand Outside diameter, mm Weight, kg/km
BUS 1*2*0,64 V К-2 8,5 65,2
No records found.

MOD_BARCODE_MOD_TITLE

MOD_BARCODE_BUHTA