Product Catalog
Budget cables

W nx0.22 CCA (M)

W nx0.22 CCA (М)

Application:

Designed for security and fire alarm systems, access control and communication systems.

Cable design:

1. Conductor: aluminum wire cladded with copper 0.60 mm.
2. Insulation: PE.
3. Shield material: aluminum foil (if needed).
4. Sheath: PVC.

Installation and operation conditions

Installation Temp Rating: -10 °C ... +50 °C;
- Operating Temp Range: -20 °C ... +60 °C.
Min Bend Radius/Minor Axis: ≥ 12 cable diameters.

Standards:

Main technical and mechanical characteristics:

Rated voltage, V 250
Test voltage, V 1500
Insulation Resistance, Mohm / km >5000
Core resistance, Ohm / km 144
Multiwire construction 7х0,20
Electrical capacity "core-core", nF / km 130

Nomenclature and mass-dimensional characteristics

Cable brand Outside diameter, mm Weight, kg/km
W 2*0,22 ССА 3,6 10,6
W 4*0,22 ССА 4,2 14,0
W 6*0,22 ССА 5,0 19,4
W 8*0,22 ССА 8,6 24,7