Solar cables for photovoltaic systems

Flexible single core photovoltaic cable halogen free H1Z2Z2-K

Кабель фотовольтаический для солнечных электростанций PV1-F

Description

Cables are designed for use in photovoltaic power supply systems: indoor and/or outdoor.
The special insulation has qualities of high abrasion resistance to high temperature..
Кабель має високий рівень стійкості до мастил, хімікатів і аміаку.
Special insulation has property of flame retardant and ozone resistance..
Cables are resistant to climatic influences, UV radiation, oils and chemicals.

Construction

1. Conductor: electrolytic tinned copper, class 5 acc. to DSTU EN 60228;
2. Insulation: halogen free cross-linked polyolefin;
3. Insulation color: natural;
4. Outer sheath: halogen free cross-linked polyolefin;
5. Sheath color: black (red, blue - upon a request).

Standards

EN 50618
DSTU EN 50618;
DSTU IEC 60332-1-2;
DSTU EN 60228;
DSTU EN 60811
DSTU 4809.

Characteristics

Rated voltage U0/U 1,0/1,0 kV AC; 1,5/1,5 kV DC
Max. voltage 1,2 kV AC;
1,8 kV DC (conductor/conductor, non-earthed system, circuit not under load)
Test voltage 6,5kV AC; 15kV DC
Flame retardant acc. to IEC 60332-1-2
Halogen free acc. to EN 50525-1, Annex B
Resistance to oil, acid and alkaline acc. to EN 60811
Ambient temperature in operation, °С from -40°С to +90°С
Ambient temperature for installation, °С from -25°С to +40°С
Max. conductor temperature, °С 90
(Max. conductor temp 120°С and at a max. amb. temp of 90 °C is limited to 20 000 h.)
Max. short-circuit temperature on conductor, °С 250 (5 sec)
Tensile rating in operation, N/ mm2 15
Min bending radius 4 diam. cable (fixed); 5 diam. cable (flexing)
Anticipated period of use 25 years

Dimensions and Weight

No. of cores X Nominal cross section Min outer diameter Nominal outer diameter Nominal weight
(N x mm2) (mm) (mm) (kg/km)
1 x 4 5,1 5,6 56
1 x 6 5,6 6,1 75
1 x 10 6,6 7,1 115

Current carrying capacity

No. of cores X Nominal cross section Current carrying capacity at +60°C amb. temp. acc. to the method of installation Short Circuit current (1 sec. 90-250°C) Electric resistant of conductor at +20°C
Single cable free in air Single cable on a surface Two loaded cables touching, on a surface
(N x mm2) (A) (A) (A) (kA) (Ω/km)
1 x 4 55 52 44 0,57 5,09
1 x 6 70 67 57 0,86 3,39
1 x 10 98 93 79 1,43 1,95

Current rating conversion factors for deviating temperatures

Ambient temperature Conversion factor
(°C)  
Up to 60 1.00
70 0.92
80 0.84
90 0.75


CERTIFICATE (download)
DATA SHEET (download)